HVAC 暖通例程 5:冷却塔风机(湿球温度 + 出水温度双条件) ​

这一页只讲这一个例程。母页 b-04-hvac 里留着例程 1,其余例程各自一页、在那一页的目录里点。

场景:冷却塔的极限出水温度由湿球温度决定(逼近度)。湿球高的时候再怎么开风机也降不下来,别白耗电。

软元件

软元件作用
D110 / D111室外温度 / 相对湿度
D133湿球温度
D120冷却塔出水温度
D261PI 输出(风机频率)
Y40工频风机
M330已接近湿球(逼近度 ≤ 3℃)

块图(照着拖即可)

例程 5:冷却塔风机(湿球温度 + 出水温度双条件) 的块图

对应的 ddc.json(点「生成 JSON」得到的就是它;也可存成 .ddc.json 导入)

json
{
  "version": 1,
  "name": "冷却塔风机",
  "scan_ms": 500,
  "lines": [
    {
      "op": "assign",
      "target": {"op":"ref","device":"D","addr":133},
      "expr": {
        "op": "hvac",
        "mode": "wetbulb",
        "args": [{"op":"ref","device":"D","addr":110},{"op":"ref","device":"D","addr":111}]
      }
    },
    {
      "op": "assign",
      "target": {"op":"ref","device":"D","addr":261},
      "expr": {
        "op": "pi",
        "id": "pi_ct",
        "args": [
          {"op":"ref","device":"D","addr":220},
          {"op":"const","value":1},
          {"op":"ref","device":"D","addr":120},
          {"op":"const","value":32},
          {"op":"const","value":1},
          {"op":"const","value":10},
          {"op":"const","value":128}
        ]
      }
    },
    {
      "op": "assign",
      "target": {"op":"ref","device":"Y","addr":40},
      "expr": {
        "op": "cmp",
        "cmp": ">",
        "args": [{"op":"ref","device":"D","addr":261},{"op":"const","value":60}]
      }
    },
    {
      "op": "assign",
      "target": {"op":"ref","device":"M","addr":330},
      "expr": {
        "op": "cmp",
        "cmp": "<=",
        "args": [
          {"op":"ref","device":"D","addr":120},
          {
            "op": "arith",
            "a": "+",
            "args": [{"op":"ref","device":"D","addr":133},{"op":"const","value":3}]
          }
        ]
      }
    }
  ]
}

要点

  • 湿球温度是冷却塔的物理下限:出水温度越接近湿球,再加大风量收效越小。用「逼近度」(出水 − 湿球)判断还有没有余量。
  • 主调节用 PI(按出水温度),保护/提示用比较(逼近度太小就别再加频率了,省电)。
  • 这个例子也演示:一个「空调参数计算」块的四个输出可以只挑一个用。

验证:室外 30℃/60% → 湿球约 23.9℃;出水 32℃ → 逼近度 8℃,PI 正常调节;把 D120 改成 26 → M330 = 1(已接近极限)。

注意事项

  • 湿球温度算错(温湿度两路之一没接准)→ 逼近度判断全错。
  • 逼近度 3℃ 是工程经验值,按塔的实际性能调,别照抄。
  • 多台塔/多台风机的轮值启停见 B2 例程 6 的轮换做法。