HVAC 暖通例程 4:露点防结露(送风温度不低于露点) ​

这一页只讲这一个例程。母页 b-04-hvac 里留着例程 1,其余例程各自一页、在那一页的目录里点。

场景:送风温度或冷冻水温度低于室内空气的露点,风口、盘管表面就会凝露滴水。用露点给送风温度设一个动态下限。

软元件

软元件作用
D110 / D111室内温度 / 相对湿度
D131露点温度
D140期望送风温度(如 14℃)
D250实际送风温度给定

块图(照着拖即可)

例程 4:露点防结露(送风温度不低于露点) 的块图

对应的 ddc.json(点「生成 JSON」得到的就是它;也可存成 .ddc.json 导入)

json
{
  "version": 1,
  "name": "露点防结露",
  "scan_ms": 500,
  "lines": [
    {
      "op": "assign",
      "target": {"op":"ref","device":"D","addr":131},
      "expr": {
        "op": "hvac",
        "mode": "dewpoint",
        "args": [{"op":"ref","device":"D","addr":110},{"op":"ref","device":"D","addr":111}]
      }
    },
    {
      "op": "assign",
      "target": {"op":"ref","device":"D","addr":250},
      "expr": {
        "op": "minmax",
        "mode": "max",
        "args": [
          {"op":"ref","device":"D","addr":140},
          {
            "op": "arith",
            "a": "+",
            "args": [{"op":"ref","device":"D","addr":131},{"op":"const","value":1}]
          }
        ]
      }
    }
  ]
}

要点

  • 「取最大」在这里就是动态下限:期望 14℃,但露点 16℃ 时送风被抬到 17℃,宁可牺牲一点冷量也不结露。
  • 余量(+1℃)按现场留:风口保温差、湿度波动大的场合留 1.5~2℃。
  • 这条是限制不是控制:它把送风温度给定"顶"上去,温度控制回路照常用这个被顶过的值。

验证:室内 26℃/60% → 露点约 17.6℃ → D250 = 18.6;把 D140 改成 20 → D250 = 20(期望值更高,不被顶)。

注意事项

  • 湿度传感器偏 5%RH,露点就偏 1~2℃:要么失效、要么天天限制冷量。湿度测点要准。
  • 只防送风温度没防冷冻水温度:盘管表面仍可能低于露点。
  • 把露点当成"目标送风温度"直接用:会变成一直在限制状态,冷量上不去。