场景:空调机组要在新风和回风之间取舍——哪一股焓值低(能量少)就多用哪一股,能省一大笔冷/热费。

软元件

软元件作用
D110 / D111新风温度 / 相对湿度
D112 / D113回风温度 / 相对湿度
D130 / D134新风焓 / 回风焓
M320新风更省
D240新风阀开度

块图(照着拖即可)

例程 3:新风 / 回风焓值比较(经济运行) 的块图

对应的 ddc.json(点「生成 JSON」得到的就是它;也可存成 .ddc.json 导入)

json
{
  "version": 1,
  "name": "焓值经济运行",
  "scan_ms": 500,
  "lines": [
    {
      "op": "assign",
      "target": {"op":"ref","device":"D","addr":130},
      "expr": {
        "op": "hvac",
        "mode": "enthalpy",
        "args": [{"op":"ref","device":"D","addr":110},{"op":"ref","device":"D","addr":111}]
      }
    },
    {
      "op": "assign",
      "target": {"op":"ref","device":"D","addr":134},
      "expr": {
        "op": "hvac",
        "mode": "enthalpy",
        "args": [{"op":"ref","device":"D","addr":112},{"op":"ref","device":"D","addr":113}]
      }
    },
    {
      "op": "assign",
      "target": {"op":"ref","device":"M","addr":320},
      "expr": {
        "op": "cmp",
        "cmp": "<",
        "args": [{"op":"ref","device":"D","addr":130},{"op":"ref","device":"D","addr":134}]
      }
    },
    {
      "op": "assign",
      "target": {"op":"ref","device":"D","addr":240},
      "expr": {
        "op": "mux",
        "args": [
          {"op":"ref","device":"M","addr":320},
          {"op":"const","value":20},
          {"op":"const","value":100},
          {"op":"const","value":0},
          {"op":"const","value":0},
          {"op":"const","value":0},
          {"op":"const","value":0},
          {"op":"const","value":0},
          {"op":"const","value":0}
        ]
      }
    }
  ]
}

要点

  • 「空调参数计算」输入温度 + 相对湿度,输出可选焓值 / 露点 / 绝对湿度 / 湿球温度——用哪个就把模式选成哪个。
  • 焓值比较的本质是"比谁带的能量少"。过渡季室外焓值常低于回风,全开新风就能免开冷水机组。
  • 新风阀最小开度(这里 20%)是卫生/新风量要求,不能为了节能关到 0。

验证:新风 18℃/50%、回风 26℃/60% → 新风焓更低 → M320 = 1、D240 = 100;把新风改成 32℃/80% → M320 = 0、D240 = 20。

注意事项

  • 湿度没接或接错:焓值算出来没有意义,温湿度两路都必须准。
  • 两颗「空调参数计算」的输出写串(新风焓写进回风的寄存器):比较结果恒定,节能逻辑形同虚设。
  • 冬夏季的判断方向按工艺定,不要照抄阈值。